R-410A ModelsService Manual 2 0 1 1HG-ServMan (1-11)SH15M30*SH20M30*Cool OnlyHazardous DutyRoom Air Conditioner* Last character may vary.

Page 2 - Table Of Contents

Permanent Split-Capacitor, totally enclosed fan motor to assure effi cient operation even under adverse electrical conditions. Motor has a s

Page 3 - IMPORTANT SAFETY INFORMATION

COMPONENT DEFINITIONSA. Mechanical componentsB. Electrical componentsC. Hermetic componentsPlenum assembly Diffuser with directional louvers used to d

Page 4 - MECHANICAL HAZARDS:

FAN MOTOR SWITCH, ON-OFF Line side SOLID STATE RELAY Load side LED indicates contacts closed when litFAN MOTORA 230 volt single phase permanent

Page 5 - INTRODUCTION

RANGE: Thermostat (Part No. 618-225-02) 60° F ( ± 2° ) to 90° F( ± 4° ) SENSING BULB LOCATION THERMOSTAT A cross ambient thermostat is used

Page 6 - S H 15 M 3 0 A - A

• R-410A pressure is approximately 60% higher than R-22 pressure.• R-410A cylinders must not be allowed to exceed 125 F, they may leak or rupture.•

Page 7 - HAZARDGARD APPLICATION

Proper refrigerant charge is essential to proper unit operation. Operating a unit with an improper refrigerant charge will result in reduced performan

Page 8 - Cooling Performance Data

3. Install a process tube to sealed system. 4. Make necessary repairs to system.5. Evacuate system to 200 microns or less. 6. Weigh in refrigeran

Page 9 - ELECTRICAL REQUIREMENTS

Undercharged Refrigerant Systems An undercharged system will result in poor performance (low pressures, etc.) in both the heating and cooli

Page 10 - HAZARDGARD SPECIAL FEATURES

Restricted Refrigerant System Troubleshooting a restricted refrigerant system can be diffi cult. The following procedures are the more common pro

Page 11 - COMPONENT DEFINITIONS

Locked Rotor Voltage (L.R.V.) Test Locked rotor voltage (L.R.V.) is the actual voltage available at the compressor under a stalled condition. Single P

Page 12 - COMPONENT TESTING

Table Of ContentsImportant Safety Information ...

Page 13 - LOW AMBIENT BYPASS VALVE

Many compressor failures are caused by the following conditions: 1. Improper air fl ow over the evaporator. 2. Overcharged refrigerant sy

Page 14

3. After all refrigerant has been recovered, disconnect suction and discharge lines from the compressor and remove compressor. Be certa

Page 15 - Refrigerant Charging

ROUTINE MAINTENANCE AIR FILTERClean the unit air intake fi lter at least every 300 to 350 hours of operation. Clean the fi lters with a mild detergent

Page 16 - Method Of Charging / Repairs

Discharge Air PlenumSlotTabLatchesReturn air grilleLatchSlotTabReturn Air GrilleROUTINE MAINTENANCE (Continued) Do not drill holes in the botto

Page 17

ROOM AIR CONDITIONER UNITPERFORMANCE TEST DATA SHEETDATE: _______________ MODEL:_______________ SERIAL:________________ YES N

Page 18

TROUBLESHOOTINGProblem Possible Cause Possible SolutionPossible SolutionPossible SolutionPossible SolutionPossible SolutionUnit does not runPower disc

Page 19 - COMPRESSOR CHECKS

Problem Possible Cause Possible SolutionPossible SolutionPossible SolutionCompressor attempts to start, or runs for short periods only. Cycles on over

Page 20 - COMPRESSOR REPLACEMENT

Problem Possible Cause Possible SolutionPossible SolutionPossible SolutionPossible SolutionFan motor does not run.Defective switch (On-Off) Check cont

Page 21

ELECTROMECHANICAL CONTROLCOOL ONLY MODELS:SH15M30*SH20M30*27*Last character may vary.

Page 22 - ROUTINE MAINTENANCE

Friedrich Air Conditioning Company10001 Reunion Place, Suite 500San Antonio, TX 782161-800-541-6645www.friedrich.comHAZARDGARD®ROOM AIR CONDITIONERSLI

Page 23

IMPORTANT SAFETY INFORMATIONThe information contained in this manual is intended for use by a qualifi ed service technician w

Page 24 - PERFORMANCE TEST DATA SHEET

TECHNICAL SUPPORT CONTACT INFORMATION29FRIEDRICH AIR CONDITIONING CO. 10001 Reunion Place, Ste. 500, San Antonio, TX 78216(210) 546-0500 877-599-5665

Page 26

HG-ServMan (1-11) FRIEDRICH AIR CONDITIONING CO. 10001 Reunion Place, Ste. 500, San Antonio, TX 78216P 210-546-0500 | F 210-546-0731 www.friedrich.c

Page 27

• Do not spray or pour water on the return air grille, discharge air grille, evaporator coil, control panel, and sleeve on the room side of the air c

Page 28 - Last character may vary

PROPERTY DAMAGE HAZARDSFIRE DAMAGE HAZARDS:• Read the Installation/Operation Manual for this air conditioning unit prior to operating.• Use air cond

Page 29 - LIMITED WARRANTY

Serial Number Decade Manufactured L=0 C=3 F=6 J=9 A=1 D=4 G=7 B=2 E=5 H=8 A A A R 00001 Production Run Number Year Man

Page 30 - CONTACT INFORMATION

UL Listed for use in Class I, Division 2, Groups A, B, C and D hazardous locations.Hazardgard is specically designed to cool living quarters, storag

Page 31

SPECIFICATIONS AND PERFORMANCE DATA7Due to continuing engineering research and technology, specL¿cations are subject to change without notice. Manufac

Page 32 - Printed in the U.S.A

ELECTRICAL DATAELECTRICAL REQUIREMENTSELECTRIC SHOCK HAZARD WARNINGTurn off electric power before service or installation.All electrical connect