Friedrich H)A09K25 User Manual

Browse online or download User Manual for Heat pumps Friedrich H)A09K25. Friedrich H)A09K25 User's Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 44
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
VPSERVMN (4-05)
MODELS
V(E,H)A09K25*** V(E,H)A09K34*** V(E,H)A09K50***
V(E,H)A12K25*** V(E,H)A12K34*** V(E,H)A12K50***
V(E,H)A18K25*** V(E,H)A18K34*** V(E,H)A18K25***
V(E,H)A24K25*** V(E,H)A24K34*** V(E,H)A24K50***
V(E,H)A24K75*** V(E,H)A24K10*** V(E,H)A24K00***
Service Manual
Single Package
Vertical Air Conditioning System
A – H Suf x Models
A SERIES
*** Digits vary with model.
Page view 0
1 2 3 4 5 6 ... 43 44

Summary of Contents

Page 1 - Service Manual

VPSERVMN (4-05)MODELS V(E,H)A09K25*** V(E,H)A09K34*** V(E,H)A09K50*** V(E,H)A12K25*** V(E,H)A12K34*** V(E,H)A12K50*** V(E,H)A18K25*** V(E,H)A18K34*

Page 2 - Table of Contents

10Heat AnticipatorsHeat anticipators are small resistance heaters (wired in series with the "W" circuit) and built into most electromechanic

Page 3 - Introduction

11Typical Electrical & Thermostat Wiring DiagramsVEA/VHA 24KL1L2QUICK DISCONNECTHERM BLUEYELLOWGREENWHITEREDCAPACITORBROWNGREEN BROWNCOMP WIRE HAR

Page 4 - Model Identifi cation Guide

12Typical Electrical & Thermostat Wiring DiagramsG & H Suffi xNOTE: THE DIAGRAM ABOVE ILLUSTRATES THE TYPICAL THERMOSTAT WIRING AND 208 VOLT T

Page 5 - ELECTRIC HEAT DATA

13Typical Electrical & Thermostat Wiring DiagramsA – E Suffi xFOR 208 VOLT MODELS ONLY:MOVE THE WHITE WIRE AS SHOWN BELOW.

Page 6

14Indoor Blower - Airfl owThe current Vert-I-Pak 9, 12, & 18 use a dual shaft, permanent split capacitor, single speed motor to drive indoor blower

Page 7

15Checking External Static PressureThe airflow through the unit can be determined by measuring the external static pressure of the system, and consult

Page 8 - Refrigeration Assembly

16Ductwork PreparationPull the fl ex duct tight. Extra fl ex duct slack can greatly increase static pressureExplanation of chartsChart A is the nominal

Page 9 - Electrical Rating Tables

17Method Of ChargingThe acceptable method for charging the Vert-I-Pak system is the Weighed in Charge Method. The weighed in charge method is applica

Page 10 - Room Thermostats

18Overcharged Refrigerant SystemsCompressor amps will be near normal or higher. Noncondensables can also cause these symptoms. To confi rm, remove some

Page 11 - VEA/VHA 24K

19All units are equipped with capillary tube metering devices.Checking for restricted capillary tubes.1. Connect pressure gauges to unit.2. Start th

Page 12 - COM. 208V 240V

2Table of ContentsIntroduction ...3Vert-I-Pak Model Number Identifi cation Guide ..

Page 13 - A – E Suffi x

20Touch Test in Heating/Cooling CycleThe only defi nite indications that the slide is in the mid-po-sition is if all three tubes on the suction side of

Page 14

21WARNINGDANGER OF BODILY INJURY OR DEATH FROM ELECTRICAL SHOCKWhen working on high voltage equipment - turn the electrical power off before attaching

Page 15 - Electric Heat Strips

22Single Phase Resistance TestRemove the leads from the compressor terminals and set the ohmmeter on the lowest scale (R x 1).Touch the leads of the o

Page 16 - Ductwork Preparation

23From the supply line on a typical 230 volt circuit, a 115 volt potential exists from the "R" terminal to ground through a possible short i

Page 17 - Method Of Charging

24Emergency Heat Switch (Defrost Thermostat) Continuity CheckElectric Heat Switch Operation (Heat Pumps Only)The electric heat switch is a dual functi

Page 18

25VEA09K00 RTA ... 80004910 ...28VEA09K00RTB ... 80004910 ...28VEA09K00RTE ...

Page 19 - Testing Coil

26VEA18K50RTG ... 80004920 ...32VEA18K50RTH ... 80004920 ...32VEA24K00RTH ...

Page 20 - Checking Reversing Valve

27(A - D Suffi x only)

Page 21 - Compressor Checks

28(A - D Suffi x only)

Page 22 - Compressor Replacement

29(A - D Suffi x only)

Page 23 - Capacitor Connections

3IntroductionThis service manual is designed to be used in conjunction with the installation manuals provided with each air conditioning system compon

Page 33

399-18 ELECTRICAL TROUBLESHOOTING CHART — COOLINGLine Voltage available at fan speed switch(on models so equipped)NO COOLINGInsure that Fuses are good

Page 34

4PRODUCT LINER = RACP = PTACE = EACV = VPAKH = SPLITSERIAL NUMBERDecade ManufacturedJ = 9 K = Not UsedL = 0MONTH MANUFACTUREDA = Jan D = Apr G = Ju

Page 35

402-TON ELECTRICAL TROUBLESHOOTING CHART — CoolingLine Voltage available at fan speed switch(on models so equipped)NO COOLINGInsure that Fuses are goo

Page 36

41REFRIGERANT SYSTEM DIAGNOSIS COOLINGTROUBLESHOOTING CHART — COOLINGTROUBLESHOOTING CHART — HEATINGREFRIGERANT SYSTEM DIAGNOSIS HEATING Low Su

Page 37

42Replace Reversing ValveNONOYESYESELECTRICAL TROUBLESHOOTING CHARTHEAT PUMPReversing Valve StuckYESReplace Solenoid CoilIs the Solenoid Coil Good?Is

Page 39 - NO COOLING

VPSERVMN (4-05)Use Factory Certifi ed Parts.FRIEDRICH AIR CONDITIONING CO.Post Office Box 1540 · San Antonio, Texas 78295-15404200 N. Pan Am Expressway

Page 40

5VEA/VHA9K-24KVEA09K VEA12K VEA18K VEA24K VHA09K VHA12K VHA18K VHA24KCOOLING DATACooling Btu/h 9500/9300 11800/11500 18000/17800 24000 9500/9300 11800

Page 41

6Model V(E,H)A09 V(E,H)A12 V(E,H)A18 V(E,H)A24Voltage (V)230 / 208 230 / 208 230 / 208 230 / 208RefrigerantR-22 R-22 R-22 R-22Chassis Width23.125&qu

Page 42 - HEAT PUMP

7*Height includes 2" high duct collar and 5/8" isolators under unit. **Normal Value Dry Coil on High Speed @ .3" ESP.MODELS V(E,H)A09K2

Page 43

8A good understanding of the basic operation of the refrigeration system is essential for the service technician. Without this understanding, accurate

Page 44 - Use Factory Certifi ed Parts

9Electrical Rating TablesNOTE: Use copper conductors ONLY Wire sizes are per NEC. Check local codes for overseas applicationsRecommended branch cir