Service ManualStandard Chassis ModelsRoom Air Conditioners115 -Vo lt: 208-230-Volt: Cool OnlySS08M10, SS10M10, SS12M10, SS14M10SS12M30, SS15M30, SM18M
9LISTEDELECTRICAL DATAELECTRIC SHOCK HAZARD WARNINGTurn off electric power before service or installation.All electrical connections and wiring
1010If you have fuses, they should be of the time delay type. Before you install or relocate this unit, be sure that the amperage rating of the circu
11Kuhl Control OptionsKühl Control OptionsThe Kühl gives you a variety of options for control, programming, and scheduling including wireless capabil
12Control Panel and Display Identication2 DIGIT DISPLAYShows Setting for:- Set Point (Temperature)- Room Temperature - Clock (AM/PM)ON / OFFTurns uni
13When in the SYSTEM COOL or HEAT or FAN ONLY mode, youcan also select FAN MODE, FAN SPEED, TIMER SCHEDULE, and . The SYSTEM
14SET POINTFAUTO FANSET POINTFAUTO FANUP and DOWN - arrows - Pressing either or button changes the system's set point (desired room temp
15the or buttons to change the setting.DIM FunctionThere are three separate display brightness levels, AUTO, 20% and full (100%). To ch
16NOTE: The schedule options 1 and 2 have factory pre-programmed settings which can only be changed by using the WiFi FriedrichLink™ adaptor
17SET POINTFAUTO FANTimer Start TimeThe display shows a normal system. Press and hold the HOUR button (Figure 4) for 3 seconds. Note: The Timer start-
1816Turning the TIMER ON once the time and day, the start and top times have been set:Press the button once and let go.NOTE: See the fol
1Table Of ContentsImportant Safety Information ...
19If the unit is operating in the TIMER or SCHEDULE mode, and you press any bytton except the button, the TIMER icon begins to
20TIMER/SCHEDULE Button - The button turns the schedule function on and off. Press the Schedule button once to turn on the Schedule (Res
21Remote Control Operation (Continued)SYSTEMSCHEDULEFAN SPEEDFRR081FAN SPEEDSCHEDULESYSTEMFAN MODEPOWERDISPLAYFAN MODEPOWERTEMPERATUREUPTEMPERATUREDOW
22UNIT OPERATIONFront Panel System Mode Sequence (TIMER/SCHEDULE = OFF)There are two system modes of operation. One for a cool only unit (see figure 1
23ELECTRONIC CONTROL SEQUENCE OF OPERATIONCompressor and Reversing Valve ControlCooling De-EnergizedEnergizedOnOnOffOffHeat - Heat PumpHeat - Electric
24Heat Control (Heat Pump Only)Satised PointHeating Mode Control OperationThere are two heating methods: Heat Pump and Electric Resistance Heat. Ther
25This heating is more complex due to the possibility of two heating methods. If the ambient indoor temperature is be-low the heat demand threshold (1
26Condition 2 If the Δ (delta) (set point temperature minus the ambient indoor temperature) is greater than 5 ˚F, then the unit will switch to electr
27Compressor Lock Out TimeThe lockout feature ensures that the compressor is de-energized for a period of time. The timer varies randomly from 180 to
28Fan Operation (Front Panel Mode)Heat – Cool – Auto – Fan OnlyModels starting with SS, SM have 4 speeds. Models with SL, and all Kuhl+ have 3 speedsN
2 IMPORTANT SAFETY INFORMATION The information contained in this manual is intended for use by a qualied service technician
29Remove the decorative front cover by using the tool provided (see gure below).Tighten the four (4) captive screws as indicated by the arrows in the
30REPLACING THE INDOOR COIL THERMISTORREPLACING THE CONTROL BOARDELECTRIC SHOCK HAZARD WARNINGDisconnect power to the unit before servicing. Fai
31Airflow Selection and AdjustmentAir flow direction adjustmentleft or right side of the discharge opening. Each of the banks of louvers can be direc
32CAPACITORSELECTRIC SHOCK HAZARD WARNINGTurn off electric power before servicing. Discharge capacitor with a 20,000 Ohm 2 Watt resistor before handli
33HEATING ELEMENTAll heat pumps and electric heat models are equipped with a heating element with the exception of model YS10M10. The othe
34If the User Interface does not turn on:1. Make sure the unit has the proper voltage and that it is turned on.2. Disconnect the User Interface’s wire
35Suction Line Evaporator Coil Metering Device Refrigerant Strainer Discharge Line Condenser Coil Compressor Refrigerant Drier Liquid Line
36• R-410A pressure is approximately 60% higher than R-22 pressure.• R-410A cylinders must not be allowed to exceed 125 F, they may leak or rupture.
37Proper refrigerant charge is essential to proper unit operation. Operating a unit with an improper refrigerant charge will result in reduced perform
38 3. Install a process tube to sealed system. 4. Make necessary repairs to system. 5. Evacuate system to 200 microns or less. 6. Weigh in refr
3• Do not spray or pour water on the return air grille, discharge air grille, evaporator coil, control panel, and sleeve on the room side of the air
39Undercharged Refrigerant SystemsAn undercharged system will result in poor performance (low pressures, etc.) in both the heating and cooling cycle
40Restricted Refrigerant SystemTroubleshooting a restricted refrigerant system can be difcult. The following procedures are the more common problems
41METERING DEVICECapillary Tube SystemsAll units are equipped with capillary tube metering devices. Checking for restricted capillary tubes. 1. Conn
42NOTE: System operating pressures must be near normal before valve can shift. REVERSING VALVE DESCRIPTION/OPERATIONThe Reversing Valve controls the d
43Reversing Valve in Heating Mode TESTING THE REVERSING VALVESOLENOID COIL The solenoid coil is an electromagnetic type coil mounted on the reversing
448. Pressurize sealed system with a combination of R-410A and nitrogen and check for leaks, using a suitable leak detector. Recover refrigerant
45Locked Rotor Voltage (L.R.V.) Test Locked rotor voltage (L.R.V.) is the actual voltage available at the compressor under a stalled condition. Single
46Single Phase Resistance Test tes dna slanimret rosserpmoc eht morf sdael eht evomeRthe ohmmeter on the lowest scale (R x 1). nommoc slanimret mo
47Recommended procedure for compressor replacement1. Be certain to perform all necessary electrical and refrigeration tests to be sure the compresso
481.2.3.4.5.ELECTRIC SHOCK HAZARD WARNINGTurn off electric power before service or installation.Failure to do so may result in personal injury, or dea
4PROPERTY DAMAGE HAZARDSFIRE DAMAGE HAZARDS:• Read the Installation/Operation Manual for the air conditioning unit prior to operating.• Use air cond
49ROUTINE MAINTENANCE COILS AND BASE PAN The indoor coil (evaporator coil), the outdoor coil (condenser coil) and base pan should be inspected period
50SLEEVE / DRAIN Inspect the sleeve and drain system periodically (at least yearly or bi-yearly) and clean of all obstructions and debris. Clean both
51ROUTINE MAINTENANCE (Continued) Standard lter cleaning, removal and installation instructions STEP 1. STEP 2.FILTERFILTERGRIPSTEP 2. Swing the f
52u Ensure that the circuit breaker(s) or fuse(s) and supply circuit wire size have been sized correctly. If the unit was supplied with a power supp
53Service and AssistanceBefore calling for service, please check the “Troubleshooting Tips” section on pages 40 and 41. This may help you to nd the
54SET POINTFAUTO FANSET POINTFAUTO FANHow to Check the Diagnostic Codes Erasing the Diagnostic CodesSee codes chart on next page.To check the active s
55ERROR CODES AND ALARM STATUSError CodeProblem Control Board's Action1Front Panel Button Stuck For More Than 20 SecondsContinue to monitor for &
56SET POINTFAUTO FANSET POINTFAUTO FANTest ModePress the , , & buttons simultaneously for 3 seconds. This will activate the
57THERMISTORS’ RESISTANCE VALUES(This Table Applies to All Thermistors) TEMP RESISTENCE (K Ohms) RESISTANCE TOLERANCE % F MAXMINMIN MAXCENTR-25
58 ROOM AIR CONDITIONER UNIT PERFORMANCE TEST DATA SHEET JOB NAME________________________________ TECHS NAME____________________________________ DA
5This service manual is designed to be used in conjunction with the installation and operation manuals provided with each air conditioning system.
59Problem Possible Cause Possible SolutionUnit does not operate. The unit is turned to the off position, Turn the unit to the on position and raise
60Problem Possible Cause Possible SolutionUnit Does Not Cool/Heat On And Off Too Frequently (continued). The outside temperature is below 60° F (16° C
61COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS esuaC elbissoP melborPCompressordoes not run Low voltage Check voltage at compressor.
62COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS Possible Solution esuaC elbissoP melborPUnit does not run Fuse blown or circuit tripped
63COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS Possible Solution esuaC elbissoP melborPCompressor runs for short periods only. Cycle
64COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS esuaC elbissoP melborPWater “spitting” into room Sublimation:When unconditioned satur
65HEAT / COOL ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS Possible SolutionPossible SolutionesuaC elbissoPmelborPRoom temperature uneven (Heatin
66 noitcAesuaC elbissoPmelborPUnit cools when heat is called forIncorrect wiring Refer to applicable wiring diagramDefective solenoid coil Check for c
67HEAT PUMP ROOM AIR CONDITIONERS: TROUBLE SHOOTING TIPSELECTRICAL TROUBLESHOOTING CHART - HEAT PUMPReversing Valve StuckReplace the Reversing ValveRe
68DISCHARGE TUBE SUCTION TUBE to Tube to OUTSIDE from Compressor Tube to INSIDE Capillary Tube Capillary Tube CompressorRIGHT Pilot LEFT Pil
6Serial Number Decade Manufactured L=0 C=3 F=6 J=9 A=1 D=4 G=7 B=2 E=5 H=8 A B A R 00001 Production Run Number Year Manufa
69ELECTRONIC CONTROL BOARD COMPONENTS IDENTIFICATIONLow Fan speedMedium Fan speedHigh Fan speedMax Fan speed(Heat+Cool units along with Cool models SL
70Kühl E-Control Service Kit 1 fo 1 egaP .oC gninoitidnoC riA hcirdeirF )21/7( 00_6589102910001 Reunion Place, Suite 500 / San Antonio, Texas 78216 (
71Kϋhl Electronic ControlCOOL ONLY ModelsSS08N10-A, SS10N10-A, SS10N10-B, SS12N10-A, SS14N10-A, SS14N10A-A, SM15N10-A, SS12N30-A, SS15N30-A, SM18M30-A
72Kϋhl Electronic ControlCOOL ONLY ModelsSL22N30-A, SL24N30-A, SL24N30-BHIGHMAXMEDIUMRSRSCF4F3F1NEUTRAL(115 V)92170021COMPL1L2 OR
73Kϋhl Electronic ControlCOOL ONLY ModelsSL28N30-A, SL28N30-B, SL28N30-CHIGHMAXMEDIUMRSRSCF4F3F1NEUTRAL(115 V)92170013COMPL1L2 OR
74Kϋhl Electronic ControlCOOL ONLY ModelsSL36N30-AHIGHMAXMEDIUMRSRSCF4F3F1NEUTRAL(115 V)92170018COMPL1L2 OR N4315LOWF22L E G E N D
75Kϋhl Electronic ControlCOOL with ELECTRIC HEAT ModelsES12N33-A, ES15N33-A, EM18N34-A, EM24M34-AMEDLOWHIGHRSRSCF1F2EH1NEUTRAL(115
76Kϋhl Electronic ControlCOOL WITH ELECTRIC HEAT ModelsEL36N35-AMEDLOWHIGHRSRSCF1F2EH1NEUTRAL(115 V)92170020COMPL1L2 OR N4315F32L
77Kϋhl Electronic ControlHEAT PUMP without ELECTRIC HEATYS10N10-AHIGHMAXMEDIUMRSRSCCOMPRESSORF4F3F1NEUTRAL(115 V)92170015COMPL1L2
78Kϋhl Electronic ControlHEAT PUMP modelsYS12N33-A, YM18M34-AMEDIUMLOWHIGHRSRSCCOMPRESSORF4F3NEUTRAL(115 V)92170016COMPL1L2 OR N43
7* Operates on 115 volt and is not equipped with supplemental heat. Will not provide heat at temperatures below 40°F.Friedrich room air conditioners a
79Kϋhl Electronic ControlHEAT PUMP modelYL24N35-AMEDIUMLOWHIGHRSRSCF4F3NEUTRAL(115 V)92170017COMPL1L2 OR N435F22- HEATER ELEMENT-
80Replacement Remote Control Configuration InstructionsFor Use with Kühl (cool only models) and Kühl + (cool & heat models), N models only. Conte
81Step 4. Using the Remote Control Increase or Decrease Keys, match the configuration number displayed on the Remote Control to the number shown
82Kühl User Interface Service Kit Replacement Instructions For Use with Kühl (cool only models) and Kühl + (cool and heat models) ATTENTION! - Please
83PARTS SECTIONKühl & Kühl+ Standard Chassis Unit Exploded Diagram
84PARTS SECTIONKühl & Kühl+ Standard Chassis Unit Exploded Diagram
85Kühl & Kühl+ Small-Chassis 2012 Parts ListItemPart NumberPart DescriptionES12N33-AES15N33-ASS08N10-ASS10N10-ASS12N10-ASS12N30-ASS14N10-ASS15N30-
86ItemPart NumberPart DescriptionES12N33-AES15N33-ASS08N10-ASS10N10-ASS12N10-ASS12N30-ASS14N10-ASS15N30-AYS10N10-AYS12N33-A162050304CONDENSOR COIL1161
87Kühl & Kühl+ Medium-Chassis 2012 Parts ListItem Part Number Part Description EM18N34-A EM24N34-A SM15N10-A SM18N30-A SM21N30-A SM24N30-A YM18N34
88ItemPart NumberPart DescriptionEM18N34-AEM24N34-ASM15N10-ASM18N30-ASM21N30-ASM24N30-AYM18N34-A161850227CONDENSOR COIL1161850140CONDENSOR COIL1116185
8Installation Information / Sleeve Dimensions* Minimum extensions when mounted in a window.** Minimum widths achieved using one side curtain assembly
89Kühl & Kühl+ Large-Chassis 2012 Parts ListItem Part Number Part Description EL25N35-A EL36N35-A SL22N30-A SL25N30-A SL28N30-A SL36N30-A YL24N35-
90Kühl & Kühl+ Large-Chassis 2012 Parts ListItem Part Number Part Description EL25N35-A EL36N35-A SL22N30-A SL25N30-A SL28N30-A SL36N30-A YL24N35-
91Addendum 1Schedule Table with Energy Saving ValuesStart Time 600 Start Time 600 Start Time 600
92 Friedrich Air Conditioning Company 10001 Reunion Place, Suite 500 San Antonio, TX 78216 800.541.6645www.friedrich.com ROOM AIR CONDITIONERS LIMITED
93Kuhl-Serv/PartsMan (9-12)FRIEDRICH AIR CONDITIONING CO. 10001 Reunion Place, Ste. 500, San Antonio, TX 78216(210) 546-0500 877-599-5665 x 261 FA
Kuhl-Serv/PartsMan (9-12)FRIEDRICH AIR CONDITIONING CO.10001 Reunion Place, Ste 500, San Antonio, TX 78216 P 210-546-0500 l F 210-546-0731 www.fried
Comments to this Manuals