Friedrich VERT-I-PAK R410A User Manual

Browse online or download User Manual for Heat pumps Friedrich VERT-I-PAK R410A. Friedrich VERT-I-PAK R410A User's Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 61
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
V(E, H)A09K25L-* V(E, H)A09K34L-* V(E, H)A09K50L-*
V(E, H)A12K25L-* V(E, H)A12K34L-* V(E, H)A12K50L-*
V(E, H)A18K25L-* V(E, H)A18K34L-* V(E, H)A18K50L-*
V(E, H)A24K25L-* V(E, H)A24K34L-* V(E, H)A24K50L-*
V(E, H)A24K75L-* V(E, H)A24K10L-*
VPK-ServMan-L (4-11)
2011-2012 Service/Parts Manual
L-B Suffi x, R410A Models
A Series (Electronic Controls)
Single Package Vertical Air Conditioning System
9-18K 24K
*Last Character May Vary
Page view 0
1 2 3 4 5 6 ... 60 61

Summary of Contents

Page 1 - Series (Electronic Controls)

V(E, H)A09K25L-* V(E, H)A09K34L-* V(E, H)A09K50L-*V(E, H)A12K25L-* V(E, H)A12K34L-* V(E, H)A12K50L-*V(E, H)A18K25L-* V(E, H)A18K34L-* V(E, H)A18

Page 2 - Table of Contents

ELECTRONIC CONTROL BOARD FEATURES The new Friedrich Vert-I-Pak has state of the art features to improve guest comfort and conserve energy. Through the

Page 3 - IMPORTANT SAFETY INFORMATION

TheNote: Unit is operated by a wired remote wall t-stat which is connected to an electronic control boardat the VPAK unit.Heat Mode in Cool with Elect

Page 4 - MECHANICAL HAZARDS:

Compressor Lock Out TimeThe lockout feature ensures that the compressor is de-energized for a period of time. The timer varies randomly from 180 to 24

Page 5 - INTRODUCTION

ELECTRIC SHOCK HAZARD WARNINGDisconnect power to the unit before servicing. Failure to follow this warning could result in serious injury or

Page 6 - Model Identifi cation Guide

SERVICECUT/SEVER HAZARD CAUTIONBe careful with the sharp edges and corners. Wear protective clothing and gloves, etc.Failure to do so could result in

Page 7 - 0141012141 01214121

VPAK 9-18K BTU UNITSCOMPONENTS IDENTIFICATION14Air IntakeGroundFront SideBlower Wheel andHeater in here10” Duct CollarRight SideLeft and Front SidesLe

Page 8 - Chassis Specifi cations

VPAK 24K BTU UNITSCOMPONENTS IDENTIFICATION15Front SideLeft and Back Sides Right SideAir IntakeCondenserAir DischargeCondenser Air IntakePull OutDisco

Page 9 - TECHNICAL SERVICE DATA

16Error Codes and Alarm StatusUnit Control PanelThe display shown below has four digits. The left two digits indicate the error code # ( 1 to 24 ), Th

Page 10 - °F the compressor is

17COMPONENTS TESTINGTesting the Diagnostic Service ModuleTesting the Electronic Control BoardIf the Diagnostic Service Module does not turn on:1. Make

Page 11

ELECTRONIC CONTROL BOARD COMPONENTS IDENTIFICATIONAND TESTING (Continued) (See wiring diagrams pages 41-46)FrontSample board for Kuhl+ unitBackVPAK 24

Page 12 - Room Air Sampling Feature

1Table of Contents 2-4 4 5 5 6788910-11 121314 15 16 1718 19-22 2324 2422-2325262627Important Safety Information ...

Page 13 - ELECTRIC SHOCK HAZARD

BLOWER / FAN MOTOR TESTBLOWER / FAN MOTORA single phase permanent split capacitor motor is used to drive the evaporator blower and condenser fan. A s

Page 14 - Warranty

DRAIN PAN VALVE During the cooling mode of operation, condensate which naf resnednoc eht yb pu dekcip si nap niard eht ni stcellocblade and sprayed

Page 15 - COMPONENTS IDENTIFICATION

EXAMPLE: Airfl ow requirements are calculated as follows: (Having a wet coil creates additional resistance to airfl ow. This addit ional resistance must

Page 16 - VPAK 24K BTU UNITS

The Vert-I-Pak A series units must be installed with a free return air configuration. The table below lists the indoor airflow at cor

Page 17 - Error Codes and Alarm Status

A good understanding of the basic operation of the refrigeration system is essential for the service technician. Without this understanding,

Page 18 - COMPONENTS TESTING

Refrigerant ChargingProper refrigerant charge is essential to proper unit opera-tion. Operating a unit with an improper refrigerant charge will result

Page 19 - Ensure it is set at

3. Install a process tube to sealed system. 4. Make necessary repairs to system.5. Evacuate system to 200 microns or less. 6. Weigh in refrigeran

Page 20 - Capacitor Connections

Overcharged Refrigerant SystemsAfter the unit has run 10 to 15 minutes, check the gauge pressures. Gauges connected to system with an underchar

Page 21

METERING DEVICE Capillary Tube Systems All units are equipped with capillary tube metering devices. Checking for restricted capillary tubes. 1.

Page 22 - External Static Pressure

NOTE: System operating pressures must be near normal before valve can shift. REVERSING VALVE DESCRIPTION/OPERATION The Reversing Valve controls

Page 23 - Chart B – Correction Multipli

IMPORTANT SAFETY INFORMATIONThe information contained in this manual is intended for use by a qualifi ed service technician w

Page 24 - Refrigeration Assembly

Reversing Valve in Heating Mode When sluggish or stuck in the mid-position, part of the discharge gas from the compressor is directed back t

Page 25 - Refrigerant Charging

8. Pressurize sealed system with a combination of R-410A and nitrogen and check for leaks, using a suitable leakdetector. Recover refrigerant p

Page 26 - Method Of Charging / Repairs

Remove the leads from the compressor terminals and set the ohmmeter on the lowest scale (R x 1). Touch the leads of the ohmmeter from terminals commo

Page 27

Recommended procedure for compressor replacement 1. Be certain to perform all necessary electrical and refrigeration tests to be sure

Page 28 - Capillary Tube Systems

1.2.3.4.5.ELECTRIC SHOCK HAZARD WARNINGTurn off electric power before service or installation.Failure to do so may result in personal injury, or death

Page 29 - TESTING THE COIL

ROOM AIR CONDITIONER UNIT PERFORMANCE TEST DATA SHEET JOB NAME________________________________ TECHS NAME____________________________________ DATE:

Page 30

THERMISTORS’ RESISTANCE VALUES(This Table Applies to All Thermistors)7(03FAHRENHEIT5(6,67$1&(.2KPV5(6,67$1&(72/(5$1&( 

Page 31 - COMPRESSOR CHECKS

ELECTRICAL TROUBLESHOOTING CHART - COOLING9K BTU, 12K BTU, & 18K BTUNO COOLING OPERATIONInsure that Fuses are good and/or that Circuit Breakers ar

Page 32 - Internal Overload

ELECTRICAL TROUBLESHOOTING CHART - COOLING24K BTUYesNo24V at t-stat andcontrol wiring?YesNo24V at t-stat andcontrol wiring?NO COOLING OPERATIONBefore

Page 33 - COMPRESSOR REPLACEMENT

ELECTRICAL TROUBLESHOOTING CHARTHEAT PUMPReplace Reversing ValveNONOYESYESReversing Valve StuckYESReplace Solenoid CoilIs the Solenoid Coil Good?Is Li

Page 34 - ROUTINE MAINTENANCE

Do not spray or pour water on the return air grille, discharge air grille, evaporator coil, control panel, • and sleeve on the room side of the air co

Page 35 - Siz ing Gu ide

REFRIGERANT SYSTEM DIAGNOSIS COOLINGREFRIGERANT SYSTEM DIAGNOSIS HEATING Low Load Conditions High Load Conditions Low Load Conditions High L

Page 36 - FAHRENHEIT

REMOTE WALL THERMOSTAT WIRING DIAGRAMS LEGEND FOR AT WIRING HARNESSRT6 - Two Speeds Fan T-Stat - Field Provided-- -- -- Field WiringC Common Term

Page 37 - NO COOLING OPERATION

COOL WITH ELECTRIC HEATELECTRICAL & THERMOSTAT WIRING DIAGRAMVEA 09/12/18 with 2.5 KW, 3.4 KW or 5KW ELECTRIC HEAT41BLUEREDWHITEGREENBROWN ORANGEC

Page 38

HEAT PUMP WITH ELECTRIC HEATELECTRICAL & THERMOSTAT WIRING DIAGRAMVHA 09/12/18 with 2.5 KW, 3.4 KW or 5KW ELECTRIC HEAT42BLUEREDWHITEBLACK GREENBR

Page 39 - HEAT PUMP

COOL WITH ELECTRIC HEATELECTRICAL & THERMOSTAT WIRING DIAGRAMVEA 24 with 2.5 KW, 3.4 KW or 5KW ELECTRIC HEAT43WHITEWHITE WHITE BLUEREDWHITEREDWHIT

Page 40

44WHITEWHITE WHITE BLUEREDWHITEREDWHITE GREENBROWN ORANGEBROWN CGREENFANHERMBLACK L1L2CELECTRONIC CONTROLHERMFANTERMINAL DETAILBLACKBLUEBLUEBLACKBLACK

Page 41

45WHITEWHITE WHITE BLUEREDWHITEREDWHITE BLACK GREENBROWN ORANGEBROWN CGREENFANHERMBLACK L1L2CELECTRONIC CONTROLHERMFANTERMINAL DETAILBLACKBLUEBLUEBLAC

Page 42 - COOL WITH ELECTRIC HEAT

HEAT PUMP WITH ELECTRIC HEATELECTRICAL & THERMOSTAT WIRING DIAGRAMVHA 24 with 7.5 KW and 10KW ELECTRIC HEAT46WHITEWHITE WHITE BLUEREDWHITEREDWHITE

Page 43 - HEAT PUMP WITH ELECTRIC HEAT

AccessoriesMODEL DESCRIPTION PHOTO VPAWP1-8VPDP1VPRG4 RT4RT6VPSC2VPAL2VPAWP1-143/4" high x 27" wide.WALL PLENUM Two-part sleeve that telesco

Page 44 - VEA 24 K

(10-06)Friedrich Air Conditioning CompanyVERT-I-PAK® A SERIES SINGLE PACKAGE VERTICAL AIR CONDITIONERSLIMITED WARRANTYSAVE THIS CERTIFICATE.It gives y

Page 45

4PROPERTY DAMAGE HAZARDSFIRE DAMAGE HAZARDS:Read the Installation/Operation Manual for this air conditioning unit prior to operating.• Use air conditi

Page 46

81910112745632011 VPAK 9K-18K BTU/h Models49

Page 47

1716121513142011 VPAK 9K-18K BTU/h Models50

Page 48 - Accessories

242625282723162011 VPAK 9K-18K BTU/h Models51

Page 49 - LIMITED WARRANTY

20212218192011 VPAK 9K-18K BTU/h Models52

Page 50 - 2011 VPAK 9K-18K BTU/h Models

Reference NumberPart Number Part DescriponVEA09K25RTL-B VEA09K34RTL-B VEA09K50RTL-B VEA12K25RTL-B VEA12K34RTL-B VEA12K50RTL-B VEA18K25RTL-B VE

Page 51

8942167532011 VPAK 24K BTU/h Models54

Page 52

181716101415231213222162019112011 VPAK 24K BTU/h Models55

Page 53

251429302426282011 VPAK 24K BTU/h Models56

Page 54

3332312011 VPAK 24K BTU/h Models57

Page 55 - 2011 VPAK 24K BTU/h Models

Reference NumberPart Number Part DescriponVEA24K10RTL-B VEA24K25RTL-B VEA24K34RTL-B VEA24K50RTL-B VEA24K75RTL-B VHA24K10RTL-B VHA24K25RTL-B VH

Page 56

ELECTRIC HEATER SIZEA-Series 00 = No electric heat 25 = 2.5 KW 34 = 3.4 KW 50 = 5.0 KW75 = 7.5 KW10 = 10 KW NOMINAL CAPACITYA-Series (Btu/h)09 = 9,0

Page 57

Printed in the U.S.A. VPK-ServMan-L (4-11) 59FRIEDRICH AIR CONDITIONING CO. 10001 Reunion Place, Ste. 500, San Antonio, TX 78216(210) 546-0500 877-

Page 58

FRIEDRICH AIR CONDITIONING CO. 10001 Reunion Place, Ste. 500, San Antonio, TX 78216P 210-546-0500 | F 210-546-0731 www.friedrich.com Printed in the U

Page 59

Wire SizeELECTRICAL REQUIREMENTSUnit MUSTSupply voltageFor VPAK Cool with Electric Heat 9-18KELECTRIC SHOCK HAZARD WARNINGTurn off electric power befo

Page 60 - CONTACT INFORMATION

Chassis Specifi cationsModel 2011 VEA09K VEA12K VEA18K VEA24K VHA09K VHA12K VHA18K VHA24KCOOLING DATACOOLING BTUh 9400/9000 11500/11200 17000/16500 230

Page 61

Extended Cooling Performance DataModel #Model #Cooling Performance DataTECHNICAL SERVICE DATAVEA - EXTENDED COOLING PERFORMANCE72 67 62 72 67 62 72 67