MULTIZONE CONFIGURATION GUIDELINES
MR36TQY3JMA:
FOR (2) ZONES:
Select any combination of (2) indoor units
per system.
FOR (3) ZONES:
Select any combination of (3) indoor units
with no more than (2) 18,000 Btu indoor
units plus (1) other indoor unit.
FOR (4) ZONES:
Select any combination of (4) indoor units.
Combinations SHOULD NOT:
Exceed the maximum allowable total
indoor unit connected capacity of
48,000 Btu.
MR24DY3JMA:
FOR (2) ZONES:
Select any combination of (2) indoor units
with a maximum (1) 18,000 Btu indoor units
plus (1) other indoor unit.
FOR (3) ZONES:
Select any combination of (3) indoor units.
Combinations SHOULD NOT:
Exceed the maximum allowable total
indoor unit connected capacity of
33,000 Btu.
MR48DEY3JM:
FOR (2) ZONES:
Select any combination of (2) indoor units
per system.
FOR (3) ZONES:
Select any combination of (3) indoor units
per system.
FOR (4) THROUGH (8) ZONES:
Please note (3) 18,000 Btu indoors equal
54,000 Btu when considering combinations
adhere to the “Connected Capacity Rule”
Combinations SHOULD NOT:
1. Exceed the maximum allowable
total indoor unit connected capacity
of 65,000 Btu.
2. Be below the minimum connectible
capacity of 24,000 Btu.
MR24DY3JMA
33,000 Btu MAX.
CONNECTED
CAPACITY
12,000
18,000
7,000
9,000
12,000
18,000
Ceiling Cassette
Wall-mounted
9,000
12,000
18,000
The Insider™
MR36TQY3JMA
48,000 Btu MAX.
CONNECTED
CAPACITY
MR48DEY3JM
65,000 Btu MAX.
CONNECTED
CAPACITY
Select a combination of indoor units that does not exceed the maximum
connected capacity, and is within the recommended parameters:
30 | FRIEDRICH J SERIES DUCTLESS