The con guration mode is used to set the RT5 to match your heating/cooling system. The RT5 functions with Friedrich PTAC models.
Ensure that the thermostat is con gured for air conditioning with ELECTRIC HEAT ONLY.
To con gure the RT5, perform the following steps:
1. Remove the cover of the thermostat by gently pulling on one of the corners.
2. S
imultaneously hold the SW5 and SW6 buttons in for 5 seconds while the RT5 is in OFF mode.
3. Press the or button to change settings within each screen.
4. Press the
SW6
button to advance to the next screen.
Note: The
SW5
button will return you to the previous screen.
5. To exit con guration mode, slide the Mode switch to Heat or Cool.
FILTER
DIFF
ROOM
SET
REMOTE
Configuration Mode
Con guration Mode Settings
The nine (9) setup screens for Con guration Mode are as follows:
1. Heat pump and Non Heat Pump – Press the
or button to con gure as heat pump, or
non-heat pump system. For heat pumps, there will be an anti-short cycle delay for heating
and cooling
• 0 = Non-heat pump system
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
2. Temperature Scale (F or C) – Choose Fahrenheit or Celsius.
Press the
or button to select.
Press the
SW6
button to advance to the next screen.