Installation and Operation ManualPTAC920-087-09 (10/10)Packaged Terminal AirConditioners & Heat Pumps
8Figure 9 DimensionsFRP007NOTE: The Wall Sleeve must behorizontally level (side-to-side)and pitched 1/4 bubble to theoutside when installed in anopeni
9FRP010NOTE: Construct wall opening to comply with all applicable building codes.MAIN STUDSJACK STUDSLINTELMOUNTINGSCREW HOLESNO HOLES IN BOTTOM OF WA
10FRP011DRAIN TUBESIDE VIEWFRONT VIEWWALL SLEEVEOPTIONAL AREAPREFERRED AREA-NO FOAM INSULATIONIF THE DRAIN MUST BELOCATED IN THE OPTIONALAREA, THE FOA
11FRP012FOAMGASKETOVERFLOWSLOTSDETAIL BDETAIL ACOVERPLATEFOAMGASKETSCREWS½” O.D. TUBEMOUNTINGPLATENUTExternal Drain (for new construction or unit rep
12PXGA Standard Grille Installation Instructions1. Remove the center support and weatherboard if still installed in the sleeve.2. Insert six plasti
13W ARNING 15/20A LCDI Device 30A LCDI Device TEST BEFORE EACH USE 1. PRESS RESET BUTT ON 2. PLUG LCDI INT O POWER RECEPT ACLE 3. PRESS TEST
14TABLE 2Model Heater kW Power Cord Kit Voltage Amperage ReceptaclePDE07K 0.0 PXPC23000 230/208 15 NEMA 6-15rPDE/PDH07K 2.0 PXPC23015 230/208 15 NEMA
153. Route the cut ends of harness through the conduit connector assembly and ex conduit sleeve. Be sure to use the supplied conduit bush
16Chassis Install PreparationCheck to be sure the wall sleeve, extension (if used), grille, and drain kit are installed properly before chassis instal
17FRP020SHIPPINGTAPEFigure 20 Shipping Tape LocationFRP021REMOVE SHIPPINGSCREW IF PRESENTFigure 21 Shipping Screw LocationFigure 22 Removing Front Pan
181. Lift unit level and slide unit into wall sleeve until from seal rests rmly against front of wall sleeve.2. Locate the four supplied chassi
19How To ConnectIMPORTANT: Please read following electrical safety data carefully.1. Remove front panel. See Figure 22.2. Remove junction box.• Rem
20Friedrich PTAC Digital Control and Unit FeaturesThe new Friedrich digital PTAC has state of the art features to improve guest comfort, indoor air qu
21Instant HeatHeat Pump ModeHeat pump models will automatically run the electric heater to quickly bring the room up to temperature when initially ene
22System ConfigurationFresh Air Vent ControlThe vent control lever is located on the left side of the unit, behind the front panel.NOTE: The vent d
23The adjustable control dip switches are located at the lower left hand portion of the digital Smart Center. The inputs are only visible and accessib
24FRP030HighMedLow FanCoolHeatFan Speed ModeTemperaturePower°F vs. °C DisplayThe unit is factory congured to display all temperatures in de
25Remote Control Thermostat InstallationInstall Thermostat1. Approximately 5 ft. from the oor.2. Close to or in a frequently used room, preferably
26Desk Control TerminalsThe Friedrich PD model PTAC has built-in provisions for connection to an external switch to control power to the unit. The swi
27q Inspect and ensure that all components and accessories have been installed properly and that they have not been damaged during the installation p
2Table of ContentsCongratulations ...
28Basic TroubleshootingCOMPLAINT CAUSE SOLUTIONUnit does not operate. ● Unit turned off. ● Turn unit on ● Thermostat is satised. ● Raise/Lower temp
29COMPLAINT CAUSE SOLUTIONUnit does not cool/heat room sufciently, or cycles on and off too frequently ● The air conditioner has insufcient heating
30New Construction AccessoriesPDXWS PDXWSEXTWALL SLEEVE Galvanized zinc coated steel is prepared in an 11-step process, then powder coated with a
31New Construction AccessoriesPXCJACONDUIT KIT WITH JUNCTION BOX Hard wire conduit kit with junction box for 208/230V and 265V units (subbase not requ
32Friedrich Air Conditioning Company10001 Reunion Place, Suite 500San Antonio, TX 78216210.357.4400www.friedrich.comROOM AIR CONDITIONERSLIMITED WARRA
33Friedrich Air Conditioning Co.10001 Reunion Place, Suite 500 • San Antonio, Texas 78216(210) 357-4400 • FAX (210) 357-4480www.friedrich.com Printed
3CongratulationsThank you for your decision to purchase Friedrich. Your new Friedrich has been carefully engineered and manufactured to give you many
4General SpecificationsInstallation Checklistq Inspect all components and accessories for damage before and after installation.q Remove the cardboar
5PTAC Installation RecommendationsPTAC units should be installed no closer than 12" apart when two units are side by side. If th
6Wall Sleeve Installation Instructions (PDXWS)NOTE: Insure that the unit is only installed in a wall structurally adequate to support the unit includ
7NOTE: Follow all wall system manufacturer installation instructions. For sunrooms and modular buildings, adhere to their installation instructions